1.Frame grade: 125A, 160A, 250A, 400A, 630A
2.Rated working voltage Ue: 400/415V, 690V
3.Breaking capacity: Covers commonly used breaks in the power distribution field: 20kA, 36kA, 50kA, 70kA, 75kA (see the parameter table for specific breaking of each frame)
4.Number of poles: 3-pole
5.Release type: single magnetic type, thermal magnetic type
6.Installation method: fixed, plug-in, drawer
1.Normal working conditions: -5~40°C For -40°C ~-5°C, 40°C ~70°C,
2.If the working environment temperature exceeds 40°C, please refer to the temperature derating coefficient table for use; Storage temperature: -40~70°C (If the storage temperature is lower than normal working conditions, the product should be returned to working conditions and left to stand for at least 24 hours before being put into use);
3.Normal operating humidity: When the ambient air humidity is +40°C, the relative humidity of the atmosphere cannot exceed 50%; if the temperature is lower, it can be used under higher relative humidity conditions;For example: at +20°C, it reaches 90%.
| NO | In(A) | Parameters | Index requirements |
| 1 | 160-630 | Overload long-delay tripping setting current (A) | 0.7~1.0ln adjustable (optional) |
| 2 | 0.8~1.0ln adjustable (optional) | ||
| 3 | Short-circuit instantaneous tripping setting current (A) | 5ln~10ln adjustable (optional) | |
| 4 | Short-circuit protection | When 0.8*(5ln/10ln), it will not work within 0.2s | |
| 5 | When 1.2*(5ln/10ln), it will work within 0.2s | ||
| 6 | 125 | Overload long-delay tripping setting current (A) | 0.7~1.0ln adjustable (optional) |
| 7 | 0.8~1.0ln adjustable (optional) |
| Type | CJMM3-125 | CJMM3-160 | CJMM3-250 | CJMM3-400/630 | ||||||
| No. of Poles | 3P | |||||||||
| Rated Current | In (A) | 16/20/25/32/40/50/63/80/100/125 | 50/63/80/100/125/140/160 | 125/140/ 160/180/200 225/250 |
225/250/315/350/400 500/630 |
|||||
| Impulse Withstand Voltage | Uimp (kV) | 8 | 10 | |||||||
| Rated Operational Voltage | Ue (V AC) | 400V/415V/690V | ||||||||
| Rated Insulation Voltage | Ui (V AC) | 800 | 1000 | |||||||
| Operational Frequency (Hz) | 50/60Hz | |||||||||
| Utilisation Category | A | |||||||||
| Reference Temperature | -5~+40°C | |||||||||
| Operating Temperature | -5~+40°C | |||||||||
| Standard | IEC60947-1/IEC60947-2 | |||||||||
| Short circuit breaking capacity level | L | H | L | H | L | H | L | H | ||
| Rated ultimate short-circuit breaking capacity (kA) |
/ | / | / | / | / | / | / | / | / | / |
| AC400/415V | 3P | 25 | 50 | 36 | 50 | 36 | 50 | 50 | 70 | |
| AC690V | 3P | / | / | 8 | 10 | 8 | 10 | 10 | 15 | |
| Rated operating short-circuit breaking capacity (kA) |
/ | / | / | / | / | / | / | / | / | / |
| AC400/415V | 3P | 15 | 36 | 20 | 36 | 20 | 36 | 36 | 50 | |
| AC690V | 3P | / | / | 4 | 5 | 4 | 5 | 7,5 | 10 | |
| Electrical Life | 5000 | 3000 | ||||||||
| IP Prolection (from front side) | IP40 | |||||||||
| Pollution Degree | III | |||||||||
| Type of Release | Single magnetic trip/thermal magnetic trip | |||||||||
| Width (3 Pole) (mm) | 75 | 90 | 107 | 150 | ||||||
| Height (mm) | 130 | 155 | 165 | 257 | ||||||
| Depth (mm) | 66 | 73 | 67,5 | 114 | ||||||