Product Detail
Product Tags
Construction and Feature
- High short-circuit capacity 6KA.
- Designed to protect circuit carrying big current up to 63A.
- Contact position indication.
- Used as main switch in household and similar installation.
Technical Data
| Standard |
IEC/EN 60898-1 |
| Rated Current |
6A,10A,16A,20A,25A,32A,40A,50A,63A |
| Rated Voltage |
230/400VAC(240/415) |
| Rated Frequency |
50/60Hz |
| Number of Pole |
1P,2P,3P,4P(1P+N,3P+N) |
| Module size |
18mm |
| Curve type |
B,C,D Type |
| Breakering capacity |
6000A |
| Optimumoperating temperature |
-5ºC to 40ºC |
| Terminal Tightening torque |
5N-m |
| Terminal Capacity(top) |
25mm² |
| Terminal Capacity(bottom) |
25mm² |
| Electro-mechanical endurance |
4000cycles |
| Mounting |
35mm DinRail |
| Suitable Busbar |
PIN Busbar |
Overload Current Protection Characteristics
| Test |
Tripping Type |
Test Current |
Initial State |
Tripping timeor Non-tripping Time Provisior |
| a |
Time-delay |
1.13In |
Cold |
t≤1h(In≤63A) |
No Tripping |
| t≤2h(ln>63A) |
| b |
Time-delay |
1.45In |
After test a |
t<1h(In≤63A) |
Tripping |
| t<2h(In>63A) |
| c |
Time-delay |
2.55In |
Cold |
1s<t<60s(In≤63A) |
Tripping |
| 1s<t<120s(In>63A) |
| d |
B curve |
3In |
Cold |
t≤0.1s |
No Tripping |
| C curve |
5In |
Cold |
t≤0.1s |
No Tripping |
| D curve |
10In |
Cold |
t≤0.1s |
No Tripping |
| e |
B curve |
5In |
Cold |
t≤0.1s |
Tripping |
| C curve |
10In |
Cold |
t≤0.1s |
Tripping |
| D curve |
20In |
Cold |
t≤0.1s |
Tripping |