1.The ambient air temperature should be -5ºC~+40ºC, with the average temperature of no higher than +35ºC within 24 hours;
2.Altitude: not higher than 2000m;
3.Atmospheric conditions: when the highest temperature is +40ºC, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature, such as 90% under 20ºC. Special measures should be taken for occasional condensation due to temperature change;
4.Pollution level: level 3;
5.Installation category: category III;
6.Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°;
7.Impact vibration: the product should be installed and used in a place without obvious shaking, impact and vibration.
| Item | CJ19-25 | CJ19-32 | CJ19-43 | CJ19-63 | CJ19-95 | CJ19-115 | CJ19-150 | CJ19-170 | |
| Controllable capacitor | 220/230V | 6.7 | 10 | 15 | 25 | 35 | 40 | 46 | 52 |
| Capacity | 380/400V | 12.5 | 20 | 25 | 50 | 60 | 70 | 80 | 90 |
| 660/690V | 18 | 35 | 45 | 60 | 105 | 120 | 140 | 156 | |
| Rated Isolation | 690 | ||||||||
| Voltage Ui V | |||||||||
| Rated Operational | 220/230V, 380/400V,660/690V | ||||||||
| Voltage Ue V | |||||||||
| Conventional thermal current Ith A | 25 | 32 | 43 | 63 | 95 | 115 | 150 | 170 | |
| Rated Operational current Ie A (380V) | 18 | 29 | 36 | 58 | 92 | 105 | 120 | 136 | |
| Restrained surge capacity | 20 Ie | ||||||||
| Controlled power voltage | 110 127 220 380 | ||||||||
| Auxiliary contact | AC-15: Ie:0.95A Ue:380/400V | ||||||||
| DC-13: Ie:0.15A Ue:220/250V | |||||||||
| Conventional thermal current Ith: 10A | |||||||||
| Operating Frequency cycles/h | 120 | ||||||||
| Electrical durability 104 | 10 | 2 | |||||||
| Mechanical durability 104 | 100 | 300 | |||||||