Technical Data
| Standard |
IEN61008-1 IEN62423 |
| Type |
Electronic type (Auxiliary Electromagnetic type) |
| Characteristics of residual operation current |
and B |
| Poles |
1P+N,3P+N |
| Rated operating break capability |
10 InA |
| Rated current (A) |
25,40,63 |
| Rated voltage |
AC 240/415 |
| Rated frequency |
50/60 HZ |
| Rated residual operation current I△n (A) |
0.03, 0.1 and 0.3 |
| Rated residual non-operating current I△nno |
0.5I△n |
| Rated limited short circuit current |
10 KA |
| Rated limited residual short circuit current l△c |
10 kA |
| Scope of residual operating current |
0.51△n~I△n |
| Wiring height |
19 mm |
| Mechanical electrical life |
4,000 cycles |
| Wiring section area of terminal |
conductor of 25 mm² and below |
| Wiring terminal |
screw terminal |
| Wiring method |
column type wiring method |
| Tightening torque |
2.0Nm |
| Installation |
Installation of 35.5mm guide rail / Vertical installation |
| Enclosure protection class |
IP20 |
Basic parameters
Rated current
of housing
grade Inm(A) |
Poles |
Frequency
(Hz) |
Rated voltage
Ue(V) |
Rated current
In(A) |
Rated residual
current(A) |
Rated limited
short circuit
current Inc(A) |
Rated limited
residual short
circuit current
I△C(A) |
| 63 |
1P+N |
50/60Hz |
240 |
25 40 63 |
0.03 0.1 0.3 |
10000 |
10000 |
| 3P+N |
415 |
Standard value of breaking time and non-operating time for pulse DC residual current and smooth DC residual current produced by rectifying circuit
| Type |
In(A) |
I△n(A) |
Standard value of breaking time and non-operating time for equality of residual
current (I△A ) and following values (S) |
| 2 I△n |
4 I△n |
10 I△n |
5A,10A,20A,50A,100A,200A |
| General type |
Any value |
Any value |
0.3 |
0.15 |
0.04 |
0.04 |
Range of tripping current(Table 1)
| Model |
Tripping current I△ /A |
| AC |
0.5 I△n<I△n |
| A |
Angle of retard |
I△n>0.01A |
I△n<0.01A |
| 0° |
0.35I△n≤I△≤1.4I△n |
0.35I△n≤I△≤2I△n |
| 90° |
0.25I△n≤I△≤1.4I△n |
0.25I△n≤I△≤2I△n |
| 135° |
0.1I△n≤I△≤1.4I△n |
0.1I△n≤I△≤2I△n |
Different from (B type) of 50/60 Hz as per frequency(Table 2)
| Frequency(Hz) |
Residual non-operating current |
Residual operating current |
| 150 |
0.5I△n |
2.4I△n |
| 400 |
0.5I△n |
6I△n |
| 1000 |
I△n |
14I△n |
Tripping scope as per smooth DC residual current (type B shall meet following requirements on the premise of type A)
- For sinusoidal AC residual current no more than 1000Hz, the trip current range between diferent frequencies according to the requirements of Table 2.With a sudden residual trip current in Table 2, the breaking time should be no more than 0.3s,The minimum no trip time of type S should be no less than 0.13s, and the maximum breaking time should not exceed 0.5s.
- lf smooth residual current 0.4 time rated residual operation current (I△n) or 10 mA smooth DC residual current (the bigger shall prevail) is overlapoed on the rated frequency AC residual current. type B RCCB shall be operated. and the AC trippind current shall be no more than l△n.
- If smooth DC residua current 0.4 tme rated residual operation current (I△n) or 10 mA smooth DC residua current (the biocer shaprevai) is overlapped on the pulse DC residual current. type B RCCB shall be operated. The tripping current of RCCB with l△n > 0.01A shall be no more than 1.4 l△n while the tripping current of RCCB with l△n≤0.01 A shall be no more than 2l△n.
- For the pulse DC residual current which is stably increased and produced by two relative rectifying circuits, type B RCCB shall be actuated within the scope of 0.5 l△n to 22 1△n Type B shall trip within the time range specified according to the Table 1,With a sudden pulsating DC residual current applied to the rectifier circuit.
- For the pulse DC residual current which is stably increased and produced by three relative rectifying circuits, type B RCCB shall be operated within the scope of 0.5 l△n to 22 1△n Type B shall trip within the time range specifed according to the Table 1,With a sudden pulsating DC residual current applied to the rectifier circuit.
- For the smooth DC residual current which is stably increased, type B RCCB shall be operated within the scope of 0.5 l△n to 22 1△n Type B shall trip within the time range specifed according to the Table 1.With a smooth DC residual current applied to the rectifier circuit.
- According to the Table 3, composit wave and initial value provided in steady.RCCB composite wave residual current range of 0.5I△n to 1.4 1△n, Sudden application of 71△n,Normally the RCCB break time should be less than 0.04s, Type S RCCB break time should be less than 0.15s.
(The component values of different frequencies in the test current & the verified correct initial value when theresidual current is increased steadily) Table 3
| The component values of different frequencies in the test current (RMS) |
The verified correct initial
value (RMS) |
| Rated Frequency |
I 1kHz |
I FMotor (10Hz) |
I △ |
| 0.138I△n |
0.138I△n |
0.035I△n |
0.2I△n |