To create much more price for clients is our company philosophy; purchaser growing is our working chase for China Suppliers 1000A Low-Voltage Switchgear Drawout Type Acb, Welcome to build the very well and extensive standing business enterprise interactions with our organization to make a wonderful long run together. customers’ pleasure is our eternal pursuit!
To create much more price for clients is our company philosophy; purchaser growing is our working chase for China Universal Circuit Breaker and Acb, To meet the requirements of individual customers for each bit more perfect service and stable quality products. We warmly welcome customers around the world to visit us, with our multi-faceted cooperation, and jointly develop new markets, create a brilliant future!
| Rated current Table 1 | ||||||||
| Rated frame current Inm A | Rated current ln A | |||||||
| 2000 | (400)630,800,1000,1250,1600,2000 | |||||||
| 3200 | 2000,2500,2900,3200 | |||||||
| 4000 | 3200,3600,4000 | |||||||
| 6300 | 4000,5000,6300 | |||||||
The rated short circuit breaking capability and short time withstand of the breakers, the arcing distance is “zero” (as the outside of the breaker is no arcing.)Table 2
| Rated frame current Inm A | 2000 | 3200 | 4000 | 6300 | ||||
| Rated limit short circuit breaking capability lcu(kA)O-CO |
400V | 80 | 80 | 100 | 120 | |||
| 690V | 50 | 50 | 75 | 85 | ||||
| Rated working short circuit breaking capability n x lcu(KA)/COS∅ |
400V | 176/0.2 | 176/0.2 | 220/0.2 | 264/0.2 | |||
| 690V | 105/0.25 | 105/0.25 | 165/0.2 | 187/0.2 | ||||
| Rated short time withstand lcw lcs(kA)O-CO-CO |
400V | 50 | 50 | 80 | 100 | |||
| 690V | 40 | 40 | 65 | 75 | ||||
| Rated short time withstand lcw (kA)———”+0.4s,O-CO |
400V | 50 | 50 | 65/80(MCR) | 85/100(MCR) | |||
| 690V | 40 | 40 | 50/65(MCR) | 65/75(MCR) | ||||
| Notice: The input and out put wire are the same for the breaking of the capability. | ||||||||
The maximum destroy power is 360W for the breakers, and in the different temperature,and rated lasting current will change.Table 3
| Ambient temperature℃ |
Rated current | |||||||
| 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | ||
| 40 | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | |
| 50 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1900A | |
| 60 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1800A | |
Intelligent over current controller protection feature and functions The setting and error.Table 4
| Long delay | Short delay | Instantaneous | Earthed error | |||||
| lr1 | lr2 | Error | lr3 | Error | lr4 | Error | ||
| (0.4-1)In | (0.4-15)In | ±10% | ln-50kA(Inm=2000A) ln-75kA(Inm=3200A) |
±15% | lnm=2000~3200A (0.2-0.8)In (1200A,160A) |
±10% | ||
| Notice:lf it has the three steps protection at the same time, the setting will not across. | ||||||||
Long delay over current inverse time ooperation features I2TL, =(1.51lr1)2tL, and its action time(1.02-2.0) Ir1, has time error is ±15%. Table 5
| 1.05Ir1 | 1.3Ir1 | 1.5Ir1 Setting time S |
15 | 30 | 60 | 120 | 240 | 480 |
| >2hno action | <1h action | 2.0Ir Setting time S | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |
To create much more price for clients is our company philosophy; purchaser growing is our working chase for China Suppliers 1000A Low-Voltage Switchgear Drawout Type Acb, Welcome to build the very well and extensive standing business enterprise interactions with our organization to make a wonderful long run together. customers’ pleasure is our eternal pursuit!
Top Suppliers China Universal Circuit Breaker and Acb, To meet the requirements of individual customers for each bit more perfect service and stable quality products. We warmly welcome customers around the world to visit us, with our multi-faceted cooperation, and jointly develop new markets, create a brilliant future!