Assume full duty to satisfy all demands of our clients; reach steady advancements by marketing the development of our purchasers; grow to be the final permanent cooperative partner of clientele and maximize the interests of customers for Mcb Elcb , Dc To Ac Power Inverter , Portable Inverter , We are sincerely looking forward to cooperate with buyers all around the world. We imagine we will satisfy you. We also warmly welcome shoppers to visit our organization and purchase our merchandise.
CE Certification Rcbo Circuit Manufacturer Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J Detail:
Construction and Feature
- Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation.
- Contact position indication
- Provides protection against indirect contact by human body
- Provides complementary protection against direct contact by human body.
- Effectively protects electric equipment against insulating failure
- Equipped with switched neutral and phase pole
- Provides protection against over-voltage
- Provides comprehensive protection to household and commercial distribution systems.
- S2 Shunt Tripper
- U2+O2 Over-voltage and under-voltage tripper
Technical Data
| Standard |
IEC61009-1/EN61009-1 |
| Type |
Electronic type |
| Residual current characteristics |
AC |
| Pole No |
1P+N |
| Tripping curve |
B, C, D |
| Rated short-circuit capacity |
6kA |
| Rated current (A) |
6A, 10A, 16A, 20A, 25A, 32A |
| Rated voltage |
230V AC |
| Rated frequency |
50/60Hz |
| Rated residual operating current(mA) |
0.03, 0.1, 0.3 |
| Tripping duration |
instantaneous≤0.1s |
| Electro-mechanical endurance |
4000 cycles |
| Connection terminal |
pillar terminal with clamp |
| Terminal Connection Height |
H1=16mm H2=21mm |
| Over-voltage tripping |
280V±5% |
| Connection capacity |
Flexible conductor 10mm² |
| Rigid conductor 16mm² |
| Installation |
On symmetrical DIN rail 35.5mm |
| Panel mounting |
Overload Current Protection Characteristics
| Test procedure |
Type |
Test Current |
Initial State |
Tripping or Non-tripping Time Limit |
Expected Result |
Remark |
| a |
B,C,D |
1.13In |
cold |
t≥1h |
no tripping |
|
| b |
B,C,D |
1.45In |
after test a |
t<1h |
tripping |
Current in the 5s in th increase of stability |
| c |
B,C,D |
2.55In |
cold |
1s<t<60s |
tripping |
|
| d |
B |
3In |
cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the current |
| C |
5In |
| D |
10In |
| e |
B |
5In |
cold |
t<0.1s |
tripping |
Turn on the auxiliary switch to close the current |
| C |
10In |
| D |
20In |
| The terminology “cold state” refes to that no load is carried before testing at the reference setting temperature. |
Residual Current Action Breaking Time
| Residual Current Action Breaking Time |
| type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
| I△n |
2 I△n |
5 I△n |
5A,10A,20A,50A,100A,200A,500A |
I△t |
|
general
type |
any
value |
any
value |
0.3 |
0.15 |
0.04 |
0.04 |
0.04 |
Max Break-time |
A Type Of Trip Current Range
| Lagangle(A) |
A Tripping Current(A) |
| Lower Limit |
Upper Limit |
| 0° |
0.35 I△n |
0.14 I△n |
| 90° |
0.25 I△n |
| 135° |
0.11 I△n |
Product detail pictures:
Related Product Guide:
We depend on sturdy technical force and continually create sophisticated technologies to meet the demand of CE Certification Rcbo Circuit Manufacturer Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J , The product will supply to all over the world, such as: Marseille, Birmingham, US, Being guided by customer demands, aiming at improving the efficiency and quality of customer service, we constantly improve products and provide more comprehensive services. We sincerely welcome friends to negotiate business and start cooperation with us. We hope to join hands with friends in different industries to create a brilliant future.
It is really lucky to meet such a good supplier, this is our most satisfied cooperation, I think we will work again!
By Gladys from Afghanistan - 2018.12.28 15:18
The company can think what our think, the urgency of urgency to act in the interests of our position, can be said this is a responsible company, we had a happy cooperation!
By Rachel from Malta - 2018.12.11 11:26