Our organization has been focusing on brand strategy. Customers' gratification is our great advertising. We also source OEM provider for Molded Breaker , Outdoor Portable Power Station , Breaker Switch , We give priority to quality and customer satisfaction and for this we follow stringent quality control measures. We have in-house testing facilities where our products are tested on every aspect at different processing stages. Owning to latest technologies, we facilitate our customers with customized production facility.
CE Certification Afdd Rcbo Manufacturer Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J Detail:
Construction and Feature
- Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation.
- Contact position indication
- Provides protection against indirect contact by human body
- Provides complementary protection against direct contact by human body.
- Effectively protects electric equipment against insulating failure
- Equipped with switched neutral and phase pole
- Provides protection against over-voltage
- Provides comprehensive protection to household and commercial distribution systems.
- S2 Shunt Tripper
- U2+O2 Over-voltage and under-voltage tripper
Technical Data
| Standard |
IEC61009-1/EN61009-1 |
| Type |
Electronic type |
| Residual current characteristics |
AC |
| Pole No |
1P+N |
| Tripping curve |
B, C, D |
| Rated short-circuit capacity |
6kA |
| Rated current (A) |
6A, 10A, 16A, 20A, 25A, 32A |
| Rated voltage |
230V AC |
| Rated frequency |
50/60Hz |
| Rated residual operating current(mA) |
0.03, 0.1, 0.3 |
| Tripping duration |
instantaneous≤0.1s |
| Electro-mechanical endurance |
4000 cycles |
| Connection terminal |
pillar terminal with clamp |
| Terminal Connection Height |
H1=16mm H2=21mm |
| Over-voltage tripping |
280V±5% |
| Connection capacity |
Flexible conductor 10mm² |
| Rigid conductor 16mm² |
| Installation |
On symmetrical DIN rail 35.5mm |
| Panel mounting |
Overload Current Protection Characteristics
| Test procedure |
Type |
Test Current |
Initial State |
Tripping or Non-tripping Time Limit |
Expected Result |
Remark |
| a |
B,C,D |
1.13In |
cold |
t≥1h |
no tripping |
|
| b |
B,C,D |
1.45In |
after test a |
t<1h |
tripping |
Current in the 5s in th increase of stability |
| c |
B,C,D |
2.55In |
cold |
1s<t<60s |
tripping |
|
| d |
B |
3In |
cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the current |
| C |
5In |
| D |
10In |
| e |
B |
5In |
cold |
t<0.1s |
tripping |
Turn on the auxiliary switch to close the current |
| C |
10In |
| D |
20In |
| The terminology “cold state” refes to that no load is carried before testing at the reference setting temperature. |
Residual Current Action Breaking Time
| Residual Current Action Breaking Time |
| type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
| I△n |
2 I△n |
5 I△n |
5A,10A,20A,50A,100A,200A,500A |
I△t |
|
general
type |
any
value |
any
value |
0.3 |
0.15 |
0.04 |
0.04 |
0.04 |
Max Break-time |
A Type Of Trip Current Range
| Lagangle(A) |
A Tripping Current(A) |
| Lower Limit |
Upper Limit |
| 0° |
0.35 I△n |
0.14 I△n |
| 90° |
0.25 I△n |
| 135° |
0.11 I△n |
Product detail pictures:
Related Product Guide:
Our firm aims to operating faithfully, serving to all of our consumers , and working in new technology and new machine continually for CE Certification Afdd Rcbo Manufacturer Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J , The product will supply to all over the world, such as: Denmark, India, Madras, We aspire to meet the demands of our customers globally. Our range of merchandise and services is continuously expanding to meet customers' requirements. We welcome new and old customers from all walks of life to contact us for future business relationships and achieving mutual success!
Goods just received, we are very satisfied, a very good supplier, hope to make persistent efforts to do better.
By Pearl from Netherlands - 2018.11.06 10:04
The after-sale warranty service is timely and thoughtful, encounter problems can be resolved very quickly, we feel reliable and secure.
By Elaine from Afghanistan - 2017.10.27 12:12