| Standard | Unit | IEC/EN 61009-1 | |||||||
| Electrical features |
Mode | Electronic type | |||||||
| Type(wave form of the earth leakage sensed) | A,AC | ||||||||
| Thermo-magnatic release characterstic | B,C | ||||||||
| Rated current in | A | 6,10,16,20,25,32,40 | |||||||
| Poles | P | 1P+N | |||||||
| Rated voltage Ue | V | 110/220,120/240 | |||||||
| Rated sensiticlity I△m | A | 0.01,0.03,0.1 | |||||||
| Rated residual making and breaking capacity I△m | A | 500 | |||||||
| Rated short-circuit capacity Icn | A | 6000 | |||||||
| Breaker time under I△m | s | ≤0.1 | |||||||
| Rated frequency | Hz | 50/60 | |||||||
| Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |||||||
| Dielectric test voltage at ind.Freq. for 1min | kV | 2 | |||||||
| lnsulation voltage Ui | 500 | ||||||||
| Pollution degree | 2 | ||||||||
| Mechanical features |
Electrical life | t | 4000 | ||||||
| Mechanical life | t | 4000 | |||||||
| Contact position indicator | Yes | ||||||||
| Protection degree | IP20 | ||||||||
| Ambient temperature (with daily average ≤35℃) |
℃ | -5~+40(Special application please refer to temperature compensation correction) |
|||||||
| Storage temperature | ℃ | -25~+70℃ | |||||||
| lnstallation | Terminal connection type | Cable/Pin-type busbar/U type busbar | |||||||
| Terminal size top / bottom for cable | mm² | 16 | |||||||
| AWG | 18-5 | ||||||||
| Terminal size top / bottom for busbar | mm² | 16 | |||||||
| AWG | 18-5 | ||||||||
| Tightening torque | N*m | 2 | |||||||
| In-Ibs. | 18 | ||||||||
| Connection | From top | ||||||||
| Mounting | Plug-in type | ||||||||