Is 6kA Enough? MCB Breaking Capacity Explained

Two numbers on an MCB get confused. The one on the handle, 16 A or 32 A or 63 A, is the overload rating. The one in the small rectangle, 4500 or 6000 or 10000, is the breaking capacity: the largest short-circuit current the device can interrupt and still be reset.

The CJM5-63 from C&J Electrical is a 6 kA miniature circuit breaker from 6 A to 63 A in one to four poles, declared to IEC/EN 60898-1 and commonly used as the incoming device of a dwelling board. What follows is the practical part: which breaking capacity belongs to which installation, and which current rating belongs to which circuit.

What the box number covers

Under IEC 60898-1 the rated short-circuit capacity, Icn, is printed in a rectangle. It is not a trip threshold. The breaker trips on overload at its rated current, and on short circuit at five to ten times that current depending on the curve. The kA figure answers one question only: when the fault current is far larger than either threshold, can the arc chamber extinguish it without the contacts welding.

⚡

Where each breaking capacity is used

Fault current falls as the cable run lengthens:

  • • 4.5 kA suits older or rural installations at the end of a long overhead service, where the measurement stays below 4.5 kA;
  • • 6 kA the standard dwelling board, typically a 10 to 25 mm² service cable 20 to 50 m from the transformer, where 1.5 to 4 kA is ordinary;
  • • 10 kA houses close to a pole or pad-mounted transformer, shops and small offices, and three-phase boards with a 63 to 125 A incomer, where 6 to 10 kA appears;
  • • 15 kA and above workshops and light industrial units at the edge of a transformer, with welding sets or several sub-mains on one busbar, where the device is usually an MCCB rather than an MCB.

Where a measured value falls between two classes, the higher one is taken; the price gap is small against the cost of a failed interruption. Cascading can justify a lower rating, but only with the manufacturer’s published pair table.

Which current rating goes on which circuit

Current rating follows the cable:

6 or 10 A: lighting on 1.0 to 1.5 mm²
16 A: single dedicated load such as a boiler
20 A: radial sockets on 2.5 mm²
32 A: ring circuits and cookers on 4 to 6 mm²
40 or 50 A: showers, cookers and EV chargers on 6 to 10 mm²
63 A: sub-main or incoming single-phase board on 10 to 16 mm²

How to check the figure on site

A loop impedance test at the board gives the prospective fault current at the point where the device sits, and that reading is compared against the kA class. If it is above the Icn of the breaker, the fault current exceeds what the device can safely interrupt: contacts can weld, the case can split, and the fault can persist after the handle has moved. Load current plays no part in this check.

Where the CJM5-63 fits

  • 6 A to 63 A in 1P, 2P, 3P and 4P including 1P+N and 3P+N
  • B, C and D curves for lighting, socket circuits and small motors
  • 18 mm per pole on 35 mm DIN rail with PIN busbar supply
  • 6 kA, which matches the standard dwelling board

Technical data

Type Miniature circuit breaker for DIN rail, 6 kA
Standard IEC/EN 60898-1
Poles and modules 1P, 2P, 3P, 4P (1P+N, 3P+N); 18 mm per pole
Rated current 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Rated voltage 230/400 V AC (240/415 V), 50/60 Hz
Breaking capacity 6,000 A (6 kA)
Trip curve B, C, D
Terminals and mounting 25 mm², 2.5 N·m; 35 mm DIN rail, PIN busbar

Note: Data as published in the CJM5-63 catalogue.