The CJMM9 series is a family of moulded case circuit breakers (MCCB) developed for both domestic and export markets. The range covers seven frame sizes from 125 A to 1600 A, with rated operating currents up to 1600 A and a maximum rated insulation voltage of 1000 V (690 V on the 125 A frame). The breakers are built for AC 50 Hz systems with a rated operating voltage of 400 V. Their job is to distribute power and to protect circuits and electrical equipment against overload, short circuit and undervoltage. The same devices can also serve as infrequent starters for motors, providing overload, short-circuit and undervoltage protection on motor circuits.
Every frame complies with IEC 60947-2. Breaking capacity is divided into two classes: M type for standard distribution boards and H type for installations with a higher prospective short-circuit current. The breakers can be mounted upright or sideways, and pole configurations run from 1P to 4P, with 1P and 2P available on the 125 A frame.
2.1 How to read the CJMM9 model code
A single code carries the complete specification of the device: frame size, breaking class, operating method, number of poles, trip type, internal accessory and rated current. Reading the code from left to right is enough to identify what is being ordered.
Table 2 Meaning of each position in the model code
| Position | Code | Meaning |
|---|---|---|
| 1–2 | CJ | Company code |
| 3 | M | Moulded case circuit breaker |
| 4–5 | M9 | Design series |
| 6–8 | 125-1600 | Frame size, rated frame current Imn (A) |
| 9 | M / H | Breaking capacity class |
| 10 | blank / P / Z | Operation: handle (blank), motor (P), rotary (Z) |
| 11 | 1 / 2 / 3 / 4 | Number of poles |
| 12 | 2 / 3 | Trip type: 2=magnetic, 3=thermal-magnetic |
| 13–14 | 0 – 90 | Internal accessory code |
| 15–18 | 32 – 1600 | Rated current In (A) |
2.2 Frame sizes, current ratings and pole options
Seven frames cover the full range. The 125 A frame is the only one offered in 1P and 2P; from 160 A upwards all frames are three- or four-pole.
Table 3 Frame sizes and rated currents
| Frame Imn (A) | Poles | Rated current In (A) | Application | Wiring |
|---|---|---|---|---|
| 125 | 1/2/3/4 | 32, 40, 50, 63, 80, 100, 125 | Distribution/Motor | Front, Panel, Plug-in |
| 160 | 3/4 | 125, 140, 160 | Distribution/Motor | Front, Panel, Plug-in |
| 250 | 3/4 | 160-250 | Distribution/Motor | Front, Panel, Plug-in |
| 400 | 3/4 | 250-400 | Distribution/Motor | Front, Panel, Plug-in |
| 630 | 3/4 | 400-630 | Distribution/Motor | Front, Panel, Plug-in |
| 800 | 3/4 | 630-800 | Distribution/Motor | Front, Panel, Plug-in |
| 1600 | 3/4 | 800-1600 | Distribution/Motor | Front, Panel, Plug-in |
Note: 1P models cannot carry internal or external accessories. Neutral pole options 4300A/B available for 4P devices.
2.3 Breaking capacity: M type and H type
Ics: Service breaking capacity (interrupt and remain serviceable).
Table 4 Breaking capacity by frame and class (Ics/Icu, kA)
| Frame (A) | M type Ics/Icu | H type Ics/Icu | Voltage |
|---|---|---|---|
| 125 | 15/18 (3P) | — | AC 400V |
| 160 | 18/25 | 25/36 | AC 400V |
| 400-800 | 35/50 | 50/65 | AC 400V |
| 1600 | 35/50 | 66/75 | AC 400V |
2.5 Overload and short-circuit trip characteristics
Trip behaviour is defined at an ambient temperature of +40 °C. The magnetic threshold for motor protection sits above normal motor starting current.
Table 6 Inverse time-delay characteristics (Distribution)
| Characteristic | Multiple of In | Conv. Time | State |
|---|---|---|---|
| Overload Long Delay | 1.05 In / 1.3 In | ≥ 1h / < 1h | Cold / Hot |
| Short Circuit Inst. | 8 In / 12 In | ≥ 0.2s / < 0.2s | Cold |
2.6 Mounting, wiring and accessories
Wiring Options
- Fixed Front: Standard for DIN-style assembly.
- Fixed Panel: Mounted on plate with rear terminals.
- Plug-in: Dedicated base for quick maintenance.
Internal Accessories
- Shunt Trip: Remote electrical opening.
- Undervoltage Release: Safety trip & closure prevention.
- Auxiliary Contacts: Status signaling (Open/Closed).
- Alarm Switch: Fault trip reporting.
How to select the right CJMM9 breaker
Frequently Asked Questions
Q: What is the difference between Icu and Ics?
Icu is the ultimate breaking capacity (limit). Ics is the service capacity (serviceable after fault). Icu is for withstand checks; Ics for continuity of service.
Q: Can the CJMM9 be used for motor protection?
Yes. Every frame is available with a motor protection trip unit designed to clear starting currents without nuisance tripping.
Q: What is the difference between fixed and plug-in versions?
Fixed is bolted/wired directly. Plug-in sits on a base for rapid exchange without disconnecting busbars.
We are a professional manufacturer focusing on low-voltage electrical components, supplying high-quality MCB, RCD and distribution accessories for worldwide distributors, electrical contractors and system integrators. Our products strictly follow international safety standards to guarantee stable circuit protection performance for household and commercial projects.