TechnicalData

NO In(A) Parameters Index requirements
1 160-630 Overload long-delay tripping setting current (A) 0.7~1.0ln adjustable (optional)
2 0.8~1.0ln adjustable (optional)
3 Short-circuit instantaneous tripping setting current (A) 5ln~10ln adjustable (optional)
4 Short-circuit protection When 0.8*(5ln/10ln), it will not work within 0.2s
5 When 1.2*(5ln/10ln), it will work within 0.2s
6 125 Overload long-delay tripping setting current (A) 0.7~1.0ln adjustable (optional)
7 0.8~1.0ln adjustable (optional)

 

Type CJMM3-125 CJMM3-160 CJMM3-250 CJMM3-400/630
No. of Poles 3P
Rated Current In (A) 16/20/25/32/40/50/63/80/100/125 50/63/80/100/125/140/160 125/140/
160/180/200
225/250
225/250/315/350/400
500/630
Impulse Withstand Voltage Uimp (kV) 8 10
Rated Operational Voltage Ue (V AC) 400V/415V/690V
Rated Insulation Voltage Ui (V AC) 800 1000
Operational Frequency (Hz) 50/60Hz
Utilisation Category A
Reference Temperature -5~+40°C
Operating Temperature -5~+40°C
Standard IEC60947-1/IEC60947-2
Short circuit breaking capacity level L H L H L H L H
Rated ultimate short-circuit
breaking capacity (kA)
/ / / / / / / / / /
AC400/415V 3P 25 50 36 50 36 50 50 70
AC690V 3P / / 8 10 8 10 10 15
Rated operating short-circuit
breaking capacity (kA)
/ / / / / / / / / /
AC400/415V 3P 15 36 20 36 20 36 36 50
AC690V 3P / / 4 5 4 5 7,5 10
Electrical Life 5000 3000
IP Prolection (from front side) IP40
Pollution Degree III
Type of Release Single magnetic trip/thermal magnetic trip
Width (3 Pole) (mm) 75 90 107 150
Height (mm) 130 155 165 257
Depth (mm) 66 73 67,5 114

CJMM3 MCCB 01