Working And Installation Conditions
- The altitude of the installation site does not exceed 2000m.
- Ambient air temperature;
- The upper limit of ambient air temperature does not exceed +40°C;
- The 24-hour average ambient air temperature does not exceed +35°C;
- The lower limit of ambient air temperature is not lower than -5°C;
- Atmospheric conditions:
- The relative humidity of the atmosphere does not exceed 50% when the ambient maximum temperature is +40°C. It can have higher relative humidity at lower temperatures. When the monthly average minimum temperature of the wettest month does not exceed +25°C, the relative humidity of the atmosphere does not exceed +25°C. The average maximum relative humidity is 90%, taking into account condensation on the product surface due to temperature changes.
- Pollution level: 3
Product Category
- According to the breaking capacity of the circuit breaker, it is divided into: a standard type (S type); b higher type (H type);
- According to the wiring method of the circuit breaker: a. Wiring in front of the board; b. Wiring behind the board; c. Plug-in type; d. Pull-out type;
- According to the operation mode: a. Direct operation by handle; b. Operation by turning handle; c. Electric operation;
- According to the number of poles: two poles; three poles; four poles;
- According to accessories: alarm contacts, auxiliary contacts, shunt release, undervoltage release;
Technical Data
Circuit breaker rating
| Model |
Frame rating
rated current
In(mA) |
Rated
current
In(A) |
Rated
working
voltage (V) |
Rated
Insulation
voltage (V) |
Rated ultimate
short circuit
breaking
capacity Icu(kA) |
Rated operating
short-circuit
breaking
capacity Ics(kA) |
Number
of
poles |
Flashover
distance
(mm) |
| CJMM3-125S |
125 |
16,20,25,32,
40,50,60,80,
100,125 |
400/415 |
1000 |
25 |
18 |
3P |
≤50 |
| CJMM3-125H |
125 |
35 |
25 |
3P |
| CJMM3-250S |
250 |
100,125,160,
180,200,225,
250 |
400/690 |
800 |
35/10 |
25/5 |
2P,3P,4P |
≤50 |
| CJMM3-250S |
250 |
600 |
50 |
35 |
Inverse time breaking action characteristics of overcurrent release of distribution circuit breaker when all poles are energized at the same time
| Test current name |
I/In |
Appointed time |
Starting state |
| Agreed no tripping current |
1.05 |
2h(In>63A),1h(In≤63A) |
Cold state |
| Agreed tripping current |
1.3 |
2h(In>63A),1h(In≤63A) |
Immediately after the sequence 1 test, start |
Inverse time breaking action characteristics of overcurrent release of circuit breaker for motor protection when all poles are energized at the same time
| Setting current |
Appointed time |
Starting state |
Remark |
| 1.0In |
>2h |
Cold state |
|
| 1.2In |
≤2h |
Immediately after the sequence 1 test, start |
|
| 1.5In |
≤4min |
cold state |
10 ≤ In ≤ 250 |
| ≤8min |
cold state |
250 ≤ In ≤ 630 |
| 7.2In |
4s≤T≤10s |
cold state |
10 ≤ In ≤ 250 |
| 6s≤T≤20s |
cold state |
250 ≤ In ≤ 800 |
The instantaneous operating characteristics of the circuit breaker for distribution are set to 10In±20%, and the instantaneous operating characteristics of the circuit breaker for motor protection are set to 12In±20%.