  • Standard:IEC60439-3
  • Electric ratings: up to 63A, 240/415V, AC 50/60Hz
  • No. of mounted units: 1, 2, 3, 4 poles
  • IP Rating:IP30
  • Material of Body: PC Fire Resistant
  • Lock available

Product Detail

Product Tags

Technical Data

  • Pole No.: 1, 1P+N, 2, 3, 3P+N, 4
  • Rated voltage: AC 230/400V
  • Rated current (A):1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63A
  • Tripping curve: B, C, D
  • High short-circuit breaking capacity (Icn): 10kA
  • Rated service short-circuit breaking capacity(Ics): 7.5kA
  • Rated frequency: 50/60Hz
  • Energy limiting class: 3
  • Rated impulse withstand voltage: 6.2kV
  • Electro-mechanical endurance: 20000
  • Contact position indication
  • Connection terminal:Screw terminal/Pillar terminal with clamp
  • Connection capacity: Rigid conductor up to 25mm²
  • Terminal Connection Height: 19mm
  • Fastening torque: 2.0Nm
  • Installation:On symmetrical DIN rail 35mm/Panel mounting

 

Power Conumption

Rated Current Range (InA) Max consumption/pole (W)
In≤10 3
10<In≤16 3.5
16<In≤25 4.5
25<In≤32 6
32<In≤40 7.5
40<In≤50 9
50<In≤63 13

 

Overload Current Protection Characteristics

Test Current Type Test procedure Initial State Tripping or Non-tripping Time Limit Expected Result Remark
A B,C,D 1.13In cold t≤1h no tripping
B B,C,D 1.45In after test a t<1h tripping Current in the 5s in th increase of stability
C B,C,D 2.55In cold 1s<t<60s(In≤32A)/1s<t<120s(n>32A) tripping
D B 3In cold t≥0.1s no tripping Turn on the auxiliary switch to
C 5In
D 10In
E B 5In t<0.1s tripping Turn on the auxiliary switch to
C 10In cold
D 20In

miniature circuit breaker cjm16-63(26)

 

 

Dimension

Model Dimensions
L(mm) W(mm) H(mm)
HAG II – 1P 34 130 60
HAG II – 2P 52 130 60
HAG II – 4P 87 130 60
HAG II – 6P 125 160 60
HAG II – 8P 160 160 60
HAG II – 12P 258 160 60
HAG II – 18P 365 160 60