Product Detail
Product Tags
Technical Data
| Standard |
IEC61008 |
| Mode |
Electro-magnetic type, electronic type |
| Residual current characteristics |
A, AC |
| Pole No |
2P, 4P |
| Rated making and breaking capacity |
500A(In=25A,40A) or 10InA(In=63A,80A,100A,125A) |
| Rated current(A) |
25, 40, 63 |
| Rated voltage |
AC 230(240)/400(415) |
| Rated frequency |
50/60Hz |
| Rated residual operating current I△n(A) |
0.03, 0.1, 0.3, 0.5 |
| Rated residual non operating current I△no |
0.5I△n |
| Rated conditional short-circuit current Inc |
10kA |
| Rated conditional residual short-circuit Current I△c |
10kA |
| Tripping duration |
instantaneous tripping ≤0.3s(0.1) |
| Residual tripping current range |
0.5I△n~I△n |
| Electro-mechanical endurance |
4000 cycles |
| Connection capacity |
Rigid conductor 25mm² |
| Terminal Connection Height |
21mm |
| Connection terminal |
Pillar terminal with clamp |
| Fastening torque |
2.0Nm |
| Installation |
On symmetrical DIN rail 35.5mm |
| Panel mounting |
| Protection class |
IP20 |
Residual Current Action Breaking Time
| Type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
| I△n |
2 I△n |
5 I△n |
5A,10A,20A,50A,100A,200A,500A |
|
| general type |
any value |
any value |
0.3 |
0.15 |
0.04 |
0.04 |
Max Break-time |
| S Type |
≥25 |
>0.03 |
0.5 |
0.2 |
0.15 |
0.15 |
Max Break-time |
| 0.13 |
0.06 |
0.05 |
0.04 |
Min non-driving time |
| The general type RCBO whose current IΔn is 0.03mA or less can use 0.25A instead of 5IΔn. |