Power Conumption
| Rated Current Range (InA) |
Max consumption/pole (W) |
| In≤10 |
3 |
| 10<In≤16 |
3.5 |
| 16<In≤25 |
4.5 |
| 25<In≤32 |
6 |
Technical Data
| Standard |
IEC/EN 60898-1 |
| Pole No |
1P+N |
| Rated voltage |
AC 230V |
| Rated Current(A) |
1A,2A,3A,4A,6A,10A,16A,20A,25A,32A |
| Tripping curve |
B, C |
| Rated service short-circuit capacity(lcs) |
6kA |
| Rated frequency |
50/60Hz |
| Electro-mechanical endurance |
10000 |
| Connection terminal |
Pillar terminal with clamp |
| Connection capacity |
Rigid conductor up to 10mm2 |
| Fastening torque |
1.2Nm |
| Installation |
On symmetrical DIN rail 35.5 mm |
| Panel mounting |
| Terminal connection height |
H = 19 mm/22mm |