The corporation keeps to the operation concept scientific management, superior quality and performance primacy, consumer supreme for Mccb Switch , Molded Breaker , Auto Recloser Rccb , Our products are widely recognized and trusted by users and can meet continuously developing economic and social needs.
China OEM Dc Rcbo Factory Residual Current Circuit Breaker with Overcurrent Protection CJL6-32 – C&J Detail:
Construction and Feature
- Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation
- Contact position indication
- Provides protection against indirect contact by human body
- Provides complementary protection against direct contact by human body
- Effectively protects electric equipment against insulating failure
- Equipped with switched neutral and phase pole
- Provides protection against over-voltage
- Provides comprehensive protection to household and commercial distribution systems
- S2 Shunt Tripper
- U2+O2 Over-voltage and under-voltage tripper
Technical Data
Standard |
IEC61009-1/EN61009-1 |
Type |
Electronic type |
Residual current characteristics |
AC |
Pole No |
1P+N |
Tripping curve |
B, C, D |
Rated short-circuit capacity |
4.5kA |
Rated current (A) |
6A, 10A, 16A, 20A, 25A, 32A |
Rated voltage |
240V AC |
Rated frequency |
50/60Hz |
Rated residual operating current(mA) |
0.03, 0.1, 0.3 |
Tripping duration |
instantaneous≤0.1s |
Electro-mechanical endurance |
4000 cycles |
Connection terminal |
pillar terminal with clamp |
Terminal Connection Height |
H1=16mm H2=21mm |
Over-voltage tripping |
280V±5% |
Connection capacity |
Flexible conductor 10mm² |
Rigid conductor 16mm² |
Installation |
On symmetrical DIN rail 35.5mm |
Panel mounting |
Overload Current Protection Characteristics
Test procedure |
Type |
Test Current |
Initial State |
Tripping or Non-tripping Time Limit |
Expected Result |
Remark |
a |
B,C,D |
1.13In |
cold |
t≤1h |
no tripping |
|
b |
B,C,D |
1.45In |
after test a |
t<1h |
tripping |
Current in the 5s in th increase of stability |
c |
B,C,D |
2.55In |
cold |
1s<t<60s(In≤32A)
1s<t<120s(32<In≤63A) |
tripping |
|
d |
B |
3In |
cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the current |
C |
5In |
D |
10In |
e |
B |
5In |
cold |
t<0.1s |
tripping |
Turn on the auxiliary switch to close the current |
C |
10In |
D |
20In |
The terminology “cold state” refes to that no load is carried before testing at the reference setting temperature. |
Residual Current Action Breaking Time
Type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
I△n |
2 I△n |
5 I△n |
5A, 10A, 20A, 50A, 100A, 200A, 500A |
I△t |
|
General
type |
Any
value |
Any
value |
0.3 |
0.15 |
0.04 |
0.04 |
0.04 |
Max Break-time |
A Type Of Trip Current Range
Lagangle(A) |
A Tripping Current(A) |
Lower Limit |
Upper Limit |
0° |
0.35 I△n |
0.14 I△n |
90° |
0.25 I△n |
135° |
0.11 I△n |
Product detail pictures:
Related Product Guide:
We constantly continually give you essentially the most conscientious client provider, plus the widly variety of designs and styles with high quality materials. These initiatives include the availability of customized designs with speed and dispatch for China OEM Dc Rcbo Factory Residual Current Circuit Breaker with Overcurrent Protection CJL6-32 – C&J , The product will supply to all over the world, such as: Cyprus, Lesotho, Barcelona, Our company now has many department, and there have more than 20 employees in our company. We set up sales shop, show room, and product warehouse. In the meantime, we registered our own brand. We have tightened inspection for quality of product.
A good manufacturers, we have cooperated twice, good quality and good service attitude.
By Alva from Casablanca - 2018.05.13 17:00
In our cooperated wholesalers, this company has the good quality and reasonable price, they are our first choice.
By Julie from Serbia - 2017.01.28 19:59