Service Environmental Conditions
- Altitude: ≤1000m; if the altitude is higher than 1000m, the rated insulation level shall be corrected accordingly;
- Ambient air temperature: Maximum 40°C, minimum -25°C, daily temperature difference 25K;
- Humidity: The average value of daily relative humidity is 95%, the average value of monthly relative humidity is 90%;
- Solar radiation intensity: 0.1W/cm²;
- Pollution class: Not less than Class IV;
- Ice thickness: ≤10mm;
- Outdoor wind speed (wind pressure): 35m/s (700Pa);
- Earthquake resistance capacity (horizontal acceleration): 0.3g.
Technical Data
| Item |
Unit |
Parameter |
| Rated frequency |
Hz |
50 |
| Rated voltage |
kV |
11/12 |
| Rated current of fuse link family series |
A |
≤100 |
≤200 |
| Rated breaking current |
kA |
12.5 |
16 |
Rated short-time power
frequency withstand voltage |
To ground (dry test/wet test) |
kV/min |
42/1 |
| Fracture (dry test/wet test) |
kV/min |
48/1 |
Lightning impulse
withstand voltage |
To ground |
kV |
75 |
| Fracture |
kV |
85 |
| Creepage distance |
mm |
≥372 (Class IV pollution prevention) |
| Mechanical life |
Times |
500 |
| Service life |
Years |
≥20 |
Note: If the altitude is higher than 1000m, the rated insulation level shall be corrected accordingly.