Generally customer-oriented, and it's our ultimate goal for being not only the most trusted, trustable and honest provider, but also the partner for our customers for Black Mcb , Dc Circuit Breaker , Current Operated Circuit Breaker , We'll do our greatto fulfill your specifications and are sincerely searching ahead to developing mutual helpful small business marriage with you!
CE Certification Rcbo Electrical Supplier Residual Current Circuit Breaker with Overcurrent Protection CJL6-32 – C&J Detail:
Construction and Feature
- Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation
- Contact position indication
- Provides protection against indirect contact by human body
- Provides complementary protection against direct contact by human body
- Effectively protects electric equipment against insulating failure
- Equipped with switched neutral and phase pole
- Provides protection against over-voltage
- Provides comprehensive protection to household and commercial distribution systems
- S2 Shunt Tripper
- U2+O2 Over-voltage and under-voltage tripper
Technical Data
Standard |
IEC61009-1/EN61009-1 |
Type |
Electronic type |
Residual current characteristics |
AC |
Pole No |
1P+N |
Tripping curve |
B, C, D |
Rated short-circuit capacity |
4.5kA |
Rated current (A) |
6A, 10A, 16A, 20A, 25A, 32A |
Rated voltage |
240V AC |
Rated frequency |
50/60Hz |
Rated residual operating current(mA) |
0.03, 0.1, 0.3 |
Tripping duration |
instantaneous≤0.1s |
Electro-mechanical endurance |
4000 cycles |
Connection terminal |
pillar terminal with clamp |
Terminal Connection Height |
H1=16mm H2=21mm |
Over-voltage tripping |
280V±5% |
Connection capacity |
Flexible conductor 10mm² |
Rigid conductor 16mm² |
Installation |
On symmetrical DIN rail 35.5mm |
Panel mounting |
Overload Current Protection Characteristics
Test procedure |
Type |
Test Current |
Initial State |
Tripping or Non-tripping Time Limit |
Expected Result |
Remark |
a |
B,C,D |
1.13In |
cold |
t≤1h |
no tripping |
|
b |
B,C,D |
1.45In |
after test a |
t<1h |
tripping |
Current in the 5s in th increase of stability |
c |
B,C,D |
2.55In |
cold |
1s<t<60s(In≤32A)
1s<t<120s(32<In≤63A) |
tripping |
|
d |
B |
3In |
cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the current |
C |
5In |
D |
10In |
e |
B |
5In |
cold |
t<0.1s |
tripping |
Turn on the auxiliary switch to close the current |
C |
10In |
D |
20In |
The terminology “cold state” refes to that no load is carried before testing at the reference setting temperature. |
Residual Current Action Breaking Time
Type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
I△n |
2 I△n |
5 I△n |
5A, 10A, 20A, 50A, 100A, 200A, 500A |
I△t |
|
General
type |
Any
value |
Any
value |
0.3 |
0.15 |
0.04 |
0.04 |
0.04 |
Max Break-time |
A Type Of Trip Current Range
Lagangle(A) |
A Tripping Current(A) |
Lower Limit |
Upper Limit |
0° |
0.35 I△n |
0.14 I△n |
90° |
0.25 I△n |
135° |
0.11 I△n |
Product detail pictures:
Related Product Guide:
The organization keeps on the procedure concept scientific management, high quality and efficiency primacy, purchaser supreme for CE Certification Rcbo Electrical Supplier Residual Current Circuit Breaker with Overcurrent Protection CJL6-32 – C&J , The product will supply to all over the world, such as: Estonia, Liberia, Croatia, We critically promise that we deliver all the customers with the good quality solutions, the most competitive prices and the most prompt delivery. We hope to win a resplendent future for customers and ourselves.
The product classification is very detailed that can be very accurate to meet our demand, a professional wholesaler.
By Lindsay from Surabaya - 2018.02.08 16:45
Product quality is good, quality assurance system is complete, every link can inquire and solve the problem timely!
By Sandra from Norwegian - 2018.12.28 15:18