Like a result of ours specialty and repair consciousness, our enterprise has won a superb popularity amid buyers everywhere in the environment for Busbar Insulator , Dc To Ac Converter Device , Power Station Power Bank , We also ensure that your choice is going to be crafted with the high good quality and dependability. Be sure to feel free of charge to contact us for additional information.
CE Certification Rcbo Electrical Supplier Residual Current Circuit Breaker with Overcurrent Protection CJL6-32 – C&J Detail:
Construction and Feature
- Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation
- Contact position indication
- Provides protection against indirect contact by human body
- Provides complementary protection against direct contact by human body
- Effectively protects electric equipment against insulating failure
- Equipped with switched neutral and phase pole
- Provides protection against over-voltage
- Provides comprehensive protection to household and commercial distribution systems
- S2 Shunt Tripper
- U2+O2 Over-voltage and under-voltage tripper
Technical Data
Standard |
IEC61009-1/EN61009-1 |
Type |
Electronic type |
Residual current characteristics |
AC |
Pole No |
1P+N |
Tripping curve |
B, C, D |
Rated short-circuit capacity |
4.5kA |
Rated current (A) |
6A, 10A, 16A, 20A, 25A, 32A |
Rated voltage |
240V AC |
Rated frequency |
50/60Hz |
Rated residual operating current(mA) |
0.03, 0.1, 0.3 |
Tripping duration |
instantaneous≤0.1s |
Electro-mechanical endurance |
4000 cycles |
Connection terminal |
pillar terminal with clamp |
Terminal Connection Height |
H1=16mm H2=21mm |
Over-voltage tripping |
280V±5% |
Connection capacity |
Flexible conductor 10mm² |
Rigid conductor 16mm² |
Installation |
On symmetrical DIN rail 35.5mm |
Panel mounting |
Overload Current Protection Characteristics
Test procedure |
Type |
Test Current |
Initial State |
Tripping or Non-tripping Time Limit |
Expected Result |
Remark |
a |
B,C,D |
1.13In |
cold |
t≤1h |
no tripping |
|
b |
B,C,D |
1.45In |
after test a |
t<1h |
tripping |
Current in the 5s in th increase of stability |
c |
B,C,D |
2.55In |
cold |
1s<t<60s(In≤32A)
1s<t<120s(32<In≤63A) |
tripping |
|
d |
B |
3In |
cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the current |
C |
5In |
D |
10In |
e |
B |
5In |
cold |
t<0.1s |
tripping |
Turn on the auxiliary switch to close the current |
C |
10In |
D |
20In |
The terminology “cold state” refes to that no load is carried before testing at the reference setting temperature. |
Residual Current Action Breaking Time
Type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
I△n |
2 I△n |
5 I△n |
5A, 10A, 20A, 50A, 100A, 200A, 500A |
I△t |
|
General
type |
Any
value |
Any
value |
0.3 |
0.15 |
0.04 |
0.04 |
0.04 |
Max Break-time |
A Type Of Trip Current Range
Lagangle(A) |
A Tripping Current(A) |
Lower Limit |
Upper Limit |
0° |
0.35 I△n |
0.14 I△n |
90° |
0.25 I△n |
135° |
0.11 I△n |
Product detail pictures:
Related Product Guide:
Our corporation has been specializing in brand strategy. Customers' gratification is our great advertising. We also source OEM company for CE Certification Rcbo Electrical Supplier Residual Current Circuit Breaker with Overcurrent Protection CJL6-32 – C&J , The product will supply to all over the world, such as: luzern, Malawi, Jakarta, Welcome to visit our company, factory and our showroom where displays various hair products that will meet your expectation. Meanwhile, it is convenient to visit our website, and our sales staff will try their good to provide you the good service. Please contact us if you need more information. Our aim is to help customers realize their goals. We are making great efforts to achieve this win-win situation.
The goods we received and the sample sales staff display to us have the same quality, it is really a creditable manufacturer.
By Jerry from Nicaragua - 2018.03.03 13:09
This is a honest and trustworthy company, technology and equipment are very advanced and the prodduct is very adequate, there is no worry in the suppliment.
By Judy from Denver - 2018.02.04 14:13