We enjoy a very good reputation among our customers for our excellent product quality, competitive price and the good service for Sine Wave Power Inverter , Modular Contactor , 25 Amp Rcd Breaker , Aggressive price with high quality and satisfying support make us earned extra customers.we wish to work along with you and request common enhancement.
CE Certification Rcbo Circuit Supplier Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J Detail:
Construction and Feature
- Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation.
- Contact position indication
- Provides protection against indirect contact by human body
- Provides complementary protection against direct contact by human body.
- Effectively protects electric equipment against insulating failure
- Equipped with switched neutral and phase pole
- Provides protection against over-voltage
- Provides comprehensive protection to household and commercial distribution systems.
- S2 Shunt Tripper
- U2+O2 Over-voltage and under-voltage tripper
Technical Data
Standard |
IEC61009-1/EN61009-1 |
Type |
Electronic type |
Residual current characteristics |
AC |
Pole No |
1P+N |
Tripping curve |
B, C, D |
Rated short-circuit capacity |
6kA |
Rated current (A) |
6A, 10A, 16A, 20A, 25A, 32A |
Rated voltage |
230V AC |
Rated frequency |
50/60Hz |
Rated residual operating current(mA) |
0.03, 0.1, 0.3 |
Tripping duration |
instantaneous≤0.1s |
Electro-mechanical endurance |
4000 cycles |
Connection terminal |
pillar terminal with clamp |
Terminal Connection Height |
H1=16mm H2=21mm |
Over-voltage tripping |
280V±5% |
Connection capacity |
Flexible conductor 10mm² |
Rigid conductor 16mm² |
Installation |
On symmetrical DIN rail 35.5mm |
Panel mounting |
Overload Current Protection Characteristics
Test procedure |
Type |
Test Current |
Initial State |
Tripping or Non-tripping Time Limit |
Expected Result |
Remark |
a |
B,C,D |
1.13In |
cold |
t≥1h |
no tripping |
|
b |
B,C,D |
1.45In |
after test a |
t<1h |
tripping |
Current in the 5s in th increase of stability |
c |
B,C,D |
2.55In |
cold |
1s<t<60s |
tripping |
|
d |
B |
3In |
cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the current |
C |
5In |
D |
10In |
e |
B |
5In |
cold |
t<0.1s |
tripping |
Turn on the auxiliary switch to close the current |
C |
10In |
D |
20In |
The terminology “cold state” refes to that no load is carried before testing at the reference setting temperature. |
Residual Current Action Breaking Time
Residual Current Action Breaking Time |
type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
I△n |
2 I△n |
5 I△n |
5A,10A,20A,50A,100A,200A,500A |
I△t |
|
general
type |
any
value |
any
value |
0.3 |
0.15 |
0.04 |
0.04 |
0.04 |
Max Break-time |
A Type Of Trip Current Range
Lagangle(A) |
A Tripping Current(A) |
Lower Limit |
Upper Limit |
0° |
0.35 I△n |
0.14 I△n |
90° |
0.25 I△n |
135° |
0.11 I△n |
Product detail pictures:
Related Product Guide:
Using a complete scientific high quality management program, great high-quality and fantastic religion, we win great track record and occupied this area for CE Certification Rcbo Circuit Supplier Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J , The product will supply to all over the world, such as: Nigeria, Atlanta, Sierra Leone, Our technical expertise, customer-friendly service, and specialized products make us/company name the first choice of customers and vendors. We are looking for your inquiry. Let's set up the cooperation right now!
It is not easy to find such a professional and responsible provider in today's time. Hope that we can maintain long-term cooperation.
By Chris from Malawi - 2018.12.22 12:52
This company conforms to the market requirement and joins in the market competition by its high quality product, this is an enterprise that have Chinese spirit.
By Arlene from Zimbabwe - 2017.03.07 13:42