1.Ambient air temperature: -5°C to 40°C, with a 24-hour average not exceeding 35°C.
2.Altitude: Installation site altitude should not exceed 2000m.
3.Atmospheric conditions: At the maximum temperature of 40°C, the relative humidity of the air at the installation site should not exceed 50%; at the minimum temperature, not exceeding 20°C, the relative humidity should not exceed 90%.
4.Installation method: Mounted on standard rail TH35-7.5.
5.Pollution degree: Level III.
6.Wiring method: Secured with screw terminals.
| Product Model | CJH2-63 | ||||
| Compliant Standards | IEC60947-3 | ||||
| Number of Poles | 1P | 2P | 3P | 4P | |
| Frame Rated Current (A) | 63 | ||||
| Electrical Characteristics | |||||
| Rated Operational Voltage (Ue) | V AC | 230/400 | 400 | 400 | 400 |
| Rated Current(In) | A | 20, 25, 32, 40, 50, 63 | |||
| Rated Insulation Voltage (Ui) | V | 500 | |||
| Rated Impulse Withstand Voltage (Uimp) | kV | 4 | |||
| Breaking Type | / | ||||
| Ultimate Breaking Capacity (Icn) | kA | / | |||
| Service Breaking Capacity (Ics % of (Icn) | / | ||||
| Curve Type | / | ||||
| Tripping Type | / | ||||
| Mechanical Life (O~CO) | Actual Average | 20000 | |||
| Standard Requirement | 8500 | ||||
| Electrical Life (O~CO) | Actual Average | 10000 | |||
| Standard Requirement | 1500 | ||||
| Control and Indication | |||||
| Auxiliary Contact | / | ||||
| Alarm Contact | / | ||||
| Shunt Release | / | ||||
| Undervoltage Release | / | ||||
| Overvoltage Release | / | ||||
| Connection and Installation | |||||
| Protection Degree | All sides | IP40 | |||
| Terminal Protection Degree | IP20 | ||||
| Handle Lock | ON/OFF position (with lock accessory) | ||||
| Wiring Capacity (mm²) | 1-50 | ||||
| Ambient Temperature (°C) | -30 to +70 | ||||
| Damp Heat Resistance | Class 2 | ||||
| Altitude (m) | ≤ 2000 | ||||
| Relative Humidity | ≤ 95% at +20°C; ≤ 50% at +40°C | ||||
| Pollution Degree | 3 | ||||
| Installation Environment | Locations without significant vibration or impact | ||||
| Installation Category | Category III | ||||
| Mounting Method | DIN Rail | ||||
| Dimensions (mm) | Width | 17.6 | 35.2 | 52.8 | 70.4 |
| Height | 82 | 82 | 82 | 82 | |
| Depth | 72.6 | 72.6 | 72.6 | 72.6 | |
| Weight | 88.3 | 177.4 | 266.3 | 353.4 | |